ALL WORK TO MATCH EXISTING
REMOVE VEGITATION
repoint as necessary using VCC mortar
To repoint masonry utilizing mortar mixed and applied per the VCC standard detail sheet (attached)
Any deteriorated, cracked, or broken bricks shall be replaced to match existing in color, size, material, porosity, detail, profile and exposure.
All reinstalled masonry must be properly "toothed in" to existing masonry wall, using VCC mortar formula (attached).

VOIDS IN THE BRICK ARE NOT TO BE FILLED WITH MORTAR. BROKEN, DETERIORATED BRICKS MUST BE REPLACED WITH BRICKS MATCHING THE PREVIOUS.

All mortar to be mixed using the VCC recipe (attached) with a maximum of 1 part Portland Cement, to 3 parts lime, to 9 parts sand, and enough water to form a workable mix. Prepackaged mixes are not permitted. The resulting mix should range in color from off-white to beige but should not be grey or white in color.

MORTAR IS NOT TO BE APPLIED OVER THE FACE OF THE BRICKS UNDER ANY CIRCUMSTANCES.

Doing so will result in a STOP WORK ORDER being placed on the property and violation case will be opened on the property.

replace attic vent door, frame and trim to match existing. paint to match exisitng
replace courtyard balcony fascia and decking.
replace approximately 8' of 1x6 balcony cieling boards
replace one column
paint to match existing
NOTE: Permit issued in response to violations. Work shall commence no less than 30 days after permit is issued. Work must be completed no less than