Remove broken bricks above second story and repair.Ref code W1BRJU
Remove and replace broken stucco on ground level using VCC approved stucco mix.
Stucco: Base coat consists of 2 coats, doubled up work of 5/8" total thickness. Proportioned as follows:
• no greater than 1:12 part Portland Cement, to
• 3 parts lime, and
• 9 parts sand,
• 6 lbs./cubic yard hair or fiber, and
• enough water to form a workable mix.
Finish coat is 1/4" in total thickness proportioned as follows:
• No more than 1 Part Portland cement,
• 3 Parts Lime,
• 9 Parts Sand,
• Enough water to form a workable mix.
PREPACKAGED MIXES ARE NOT PERMITTED.
LATH OF ANY KIND IS NOT ALLOWED.
To repoint masonry utilizing mortar mixed and applied per the VCC standard detail sheet (attached)
Any deteriorated, cracked, or broken bricks shall be replaced to match existing in color, size, material, porosity, detail, profile and exposure.
All reinstalled masonry must be properly "toothed in" to existing masonry wall, using VCC mortar formula (attached).
VOIDS IN THE BRICK ARE NOT TO BE FILLED WITH MORTAR. BROKEN, DETERIORATED BRICKS MUST BE REPLACED WITH BRICKS MATCHING THE PREVIOUS.
All mortar to be mixed using the VCC recipe (attached) with a maximum of 1 part Portland Cement, to 3 parts lime, to 9 parts sand, and enough water to form a workable mix. Prepackaged mixes are not permitted. The resulting mix should range in color from off-white to beige but should not be grey or white in color.